Skip to main content
AllDigital

Back

Product code: #ALL-002008

Fire detector unipos FD7120M - Heat Detector

UniPOS

Fire detector unipos FD7120M - Heat Detector

  • Fire Device TypeAddressable heat detector with short-circuit isolator
36.83 ₾

VAT included

  • Out of stock

This model is not in stock at any branch right now.


Similar, in stock

From the same category, closest in specs and price

Compare all four


Installation request
PaymentBy cardBy bank transfer
Datasheet (opens in a new tab)

Related products

Description

The UniPOS FD7120M is a heat detector for addressable fire alarm systems. It connects to its base with a two-wire line and works from a supply voltage of (18-30)V DC.

The detector has a programmable temperature class of A2R or A2S according to EN54-5:2017 + A1:2018. It covers a circle with a diameter of 10 m and can be mounted at heights up to 8 m, both according to EN 54-14. Two status LEDs show the duty, alarm and fault conditions.

Key features:

  • Supply voltage: (18-30)V DC
  • Current consumption: not more than 300 μA in duty mode and (2±1) mA in alarm mode, with (2±1) mA from the RI/KL output in alarm mode
  • Programmable temperature class A2R or A2S according to EN54-5:2017 + A1:2018
  • Protected area: circle with a diameter of 10 m, mounting height up to 8 m (according to EN 54-14)
  • Status LEDs: both flash briefly every 12s in duty mode, light continuously in alarm, and flash at 2Hz (activated isolator) or 0.5Hz (short circuit in the remote indicator output) in fault conditions
  • Operating temperature from minus 10°C to plus 55°C, humidity resistance (93±3)% at 40°C
  • Dimensions with base: Ø100 mm, h 47mm; weight with base: >0.100 kg; base connection with two-wire, single-core or multi-core insulated, shielded wire of (0.8-1.5) mm2

Power & Protection

Operating Voltage
18–30 V DC
Standby Current
≤ 300 µA
Alarm Current
(2±1) mA

Overview

Fire Device Type
Addressable heat detector with short-circuit isolator
System Type
Addressable

Detection

Detector Technology
Heat
Temperature Class
A2R or A2S (programmable)

Compliance

Protocol
UniTALK

Physical

Operating Temperature
-10 … +55 °C (14 … 131 °F)
Mounting
Fitted on base 7100
Dimensions
Ø100 × 47 mm (Ø3.94 × 1.85 in)

Full specification

Manufacturer data, 16 parameters

Technical Features

Supply voltage
(18-30)V DC
Current Consumption in Duty Mode
not more than 300 μA
Current Consumption in Alarm Condition
(2±1) mA
Current in Alarm Condition from Output RI/KL
(2±1) mA
Time to Enter Duty Mode after Power Supply is ON
up to 30s
Reset Time
5s
Time to Enter Duty Mode after Reset
up to 40s
Status LED
Duty Mode - both LEDs flash briefly every 12s;
Alarm Condition - both LEDs produce continuous light;
Fault Condition (activated isolator) - both LEDs flash briefly with 2Hz frequency;
Fault Condition (short circuit in the remote indicator output) - both LEDs flash briefly with 0.5Hz frequency
Protected Area
circle with diameter 10 m (acc. EN 54-14)
Height of Mounting
up to 8 m (acc. EN 54-14)
Operational Temperature Range
minus 10°C - plus 55°C
Relative Humidity Resistance
(93±3)% at 40°C
Dimensions, Base Included
Ø100 mm, h 47mm
Weight, Base Included
>0.100 kg
Type of the Connecting Line to the Base
two-wire, a single-core or multi-core insulated, shielded wire
Cross Section of the Connecting Wire
(0.8-1.5) mm2