Skip to main content
AllDigital

Fire alarm control panel FS4000/4

UniPOS

Fire alarm control panel FS4000/4

372.33 ₾

VAT included

  • In stock
372.33 ₾

VAT included

  • In stock
Quantity
1

1 in stock

Installation request
PaymentBy cardBy bank transfer
Datasheet (opens in a new tab)

Compare with similar

Full comparison

Description

UniPOS FS4000/4 is a non-addressable fire control panel. It monitors fire detection lines with 2-wire installation, supports up to 32 fire detectors per loop and accepts a maximum loop resistance of 100Ω. It tells line states apart by current: 0-6 mA is a fault, 6-16 mA is standby, 16-80 mA is a fire and more than 80 mA is a short circuit.

The panel shows registered events with LED indication and a built-in buzzer. It runs from a (187 - 252)V AC supply at 50/60 Hz and has 2 backup lead gel batteries. In the 4 line configuration it draws less than 45 mA at 24V DC on the backup batteries.

Key features:

  • Fire detection lines: 2-wire installation, up to 32 fire detectors per loop, maximum loop resistance 100Ω
  • 2 controlled fire alarm lines (EN54-2, Type C): potential, relay with independent control, (19-27.5)V DC / 1A
  • 1 general fault warning relay output: potential-free, switching, 3A / 125V AC and 3A / 30V DC
  • Backup power: 2 lead gel batteries, 12V nominal, (7.0) Ah capacity C20, 28V DC charging voltage
  • Power for external devices: (19-27) V DC
  • Functions: direct mode (skip delay) for each fire detection line, logical "AND" scenario for fire detection lines, test mode for fire alarm lines, detection of a removed fire detector, input for remote reset, and an optional fire output delay of 1, 2, 3, 4, 5, 6 or 7 minutes
  • Dimensions 304mm x 222mm x 94mm, weight 980 g (34.57 oz), with the optional zone dedicated relay module FD4201

Physical

Weight
980 g (34.57 oz)

Full specification

Manufacturer data, 31 parameters

Fire Detection Lines

Maximum Number of Fire Detectors in a Line
32
Type of the Installation
two-wire
Maximum Resistance of a Line
100Ω

Thresholds Current Values

Fault Condition
0-6 mA
Duty Mode
6-16 mA
Fire Condition
16-80 mA
Short Circuit
> 80 mA

Monitored Fire Alarm Lines (EN54-2, Type C)

Number
2 pcs
Type
potential, relay with independent control
Electrical Characteristics
(19-27.5)V DC / 1A

Common Fault Warning Relay Outputs

Number
1 pcs
Type
potential-free, switching
Electrical Characteristics
3A / 125V AC,3A / 30V DC

Indication of Registered Events

Light Indication
LED
Sound
built-in buzzer

Power Supply

Voltage
(187 - 252)V AC
Frequency
50/60 Hz

Backup Batteries

Battery Type
lead, gel electrolyte
Number of Batteries
2 pcs
Nominal Voltage of the Backup Battery
12V
Nominal Capacity C20
(7.0) Ah
Charge Voltage
28V DC

Operation in Duty Mode Upon Interruption in Main Power Supply

Lines 24V / 1.2 Ah - 4 Lines
24 h
Lines 24V / 4.5 Ah - 4 Lines
98 h
Lines 24V / 7.0 Ah - 4 Lines
24 h

Consumption on Backup Batteries Supply

Configuration of 4 Lines
< 45 mA at 24V DC

Power Supply to External Devices

Voltage
(19-27) V DC

Fuses

Main Supply 230V
4.0 A
Backup Battery
6.0 A

Technical Features

Dimensions
304mm x 222mm x 94mm

Functional Data

Functional Data
identification of manual call points;
zone dedicated label and Zone dedicated LED indication for fire, fault, disable;
detection for removed fire detector;
automatic reset of the fault warning condition;
logical “AND” scenario for fire detection lines;
EN54-2 Disabled condition and Test condition per fire detection line and fire alarm line;
direct mode (skip delay) function for each fire detection line;
test-LED functionality;
built-in buzzer for fire and fault condition – one tonal, continuous, can be suppressed;
test mode for fire alarm lines;
input for remote Reset fires operation;
8 types optional scenarios for common fire out-puts and fire alarm outputs;
optional delay time for fire outputs activation 1,2,3,4,5,6 or 7 minutes;
evacuation condition - available on access level 2;
optional zone dedicated relay module FD4201, each relay is common fire output corresponding to the relevant fire detection zone

Related products