Skip to main content
AllDigital

Fire alarm control panel FS4000/8

UniPOS

Fire alarm control panel FS4000/8

484.21 ₾

VAT included

  • In stock
484.21 ₾

VAT included

  • In stock
Quantity
1

1 in stock

Installation request
PaymentBy cardBy bank transfer
Datasheet (opens in a new tab)

Compare with similar

Full comparison

Description

The UniPOS FS4000/8 is a non-addressable fire control panel for two-wire fire detection lines. Each line supports up to 32 fire detectors with a maximum loop resistance of 100Ω. The panel reads the line current to determine its state: 0-6 mA is a fault, 6-16 mA is standby, 16-80 mA is a fire, and more than 80 mA is a short circuit.

Registered events are shown by LED indication and a built-in buzzer. The panel runs from a (187 - 252)V AC, 50/60 Hz supply and has 2 lead gel backup batteries of 12V and (7.0) Ah each. In the 8 line configuration, it draws less than 65 mA at 24V DC on battery power. It measures 304mm x 222mm x 94mm and weighs 980 g (34.57 oz).

Key features:

  • Two-wire detection lines with up to 32 fire detectors per line and a maximum loop resistance of 100Ω
  • 2 controlled fire alarm lines (EN54-2, Type C): potential, relay with independent control, (19-27.5)V DC / 1A
  • 1 general fault warning relay output: potential-free, switching, rated 3A / 125V AC and 3A / 30V DC
  • Backup power from 2 lead gel batteries, 12V, (7.0) Ah (C20), with a charging voltage of 28V DC and an external device supply of (19-27) V DC
  • Identification of manual call points, detection of a removed fire detector, automatic reset of the fault warning condition, and a logical "AND" scenario for fire detection lines
  • Direct mode (skip delay) for each fire detection line, 8 types of optional scenarios for common fire outputs and fire alarm outputs, and an optional fire output activation delay of 1, 2, 3, 4, 5, 6 or 7 minutes
  • Zone dedicated label and LED indication for fire, fault and disable, EN54-2 Disabled and Test conditions, a remote Reset input, and an optional zone dedicated relay module FD4201

Physical

Weight
980 g (34.57 oz)

Full specification

Manufacturer data, 28 parameters

Fire Detection Lines

Maximum Number of Fire Detectors in a Line
32
Type of the Installation
two-wire
Maximum Resistance of a Line
100Ω

Thresholds Current Values

Fault Condition
0-6 mA
Duty Mode
6-16 mA
Fire Condition
16-80 mA
Short Circuit
> 80 mA

Monitored Fire Alarm Lines (EN54-2, Type C)

Number
2 pcs
Type
potential, relay with independent control
Electrical Characteristics
(19-27.5)V DC / 1A

Common Fault Warning Relay Outputs

Number
1 pcs
Type
potential-free, switching
Electrical Characteristics
3A / 125V AC,3A / 30V DC

Indication of Registered Events

Light Indication
LED
Sound
built-in buzzer

Power Supply

Voltage
(187 - 252)V AC
Frequency
50/60 Hz

Backup Batteries

Battery Type
lead, gel electrolyte
Number of Batteries
2 pcs
Nominal Voltage of the Backup Battery
12V
Nominal Capacity C20
(7.0) Ah
Charge Voltage
28V DC

Consumption on Backup Batteries Supply

Configuration of 8 Lines
< 65 mA at 24V DC

Power Supply to External Devices

Voltage
(19-27) V DC

Fuses

Main Supply 230V
4.0 A
Backup Battery
6.0 A

Technical Features

Dimensions
304mm x 222mm x 94mm

Functional Data

Functional Data
identification of manual call points;
zone dedicated label and Zone dedicated LED indication for fire, fault, disable;
detection for removed fire detector;
automatic reset of the fault warning condition;
logical “AND” scenario for fire detection lines;
EN54-2 Disabled condition and Test condition per fire detection line and fire alarm line;
direct mode (skip delay) function for each fire detection line;
test-LED functionality;
built-in buzzer for fire and fault condition – one tonal, continuous, can be suppressed;
test mode for fire alarm lines;
input for remote Reset fires operation;
8 types optional scenarios for common fire outputs and fire alarm outputs;
optional delay time for fire outputs activation 1,2,3,4,5,6 or 7 minutes;
evacuation condition - available on access level 2;
optional zone dedicated relay module FD4201, each relay is common fire output corresponding to the relevant fire detection zone

Related products