Power & Protection
- Mains Voltage
- 220/230 VAC, 50/60 Hz
Overview
- Fire Device Type
- Interactive fire control panel, 2 signal loops
- System Type
- Addressable
Detection
- LED Indicator
- LED indication of main events and conditions;
graphic LCD touch-screen
System Capacity
- Loops
- 2
- Devices per Loop
- 125
- Devices per Zone
- 60
- Network Panels
- Network operation with FS5200E fire extinguishing control panel
Battery
- Battery Backup
- 2 × 12 VDC, 18 Ah
Technical Data
- Fire Alarm Loops
- signal: 2;
power: 1 - Addressable Devices in One Signal Loop
- Up to 125
- Cross Section of the Signal Loop Wire
- (0.5-2.5) mm2
- Maximum Resistance of the Signal Loop
- 100Ω
- Number of Devices in One Branch
- Up to 32
- Fire Alarm Zones
- Up to 250
- Addressable Devices in One Zone
- Up to 60
- Response Time to Activated Detector Signal
- Up to 10 seconds
- Registered Events by the Counter of Fire Events
- Up to 9999
- Registered Events by the None Voltage Archive Memory
- Up to 1023
- Power Supply
- mains: 220/230VAC, 50/60Hz;
backup batteries: 2×12 VDC, 18Ah - Current Consumption of Power Supply Loop
- Up to 1A
- Outputs
- monitored, potential 28V DC/1A: 2;
auxiliary supply 24VDC/1A: 1 - Interfaces
- RS 232 or RS 485: 1;
CAN: 2 - Dimensions
- 480 x 445 x 100 mm
- Relative Humidity
- (93±3) % at 40°C
- Degree of Protection
- IP 40